Oil System Upgrades
Return to No-Regrets Remodeling index
There are many ways to improve the efficiency of an old oil boiler or furnace. First, find out if your system is oversized. A properly sized oil burner should run 45 to 50 minutes per hour when the temperature outside is the lowest it gets in your area. To downsize, ask your contractor to replace the existing oil burner nozzle with a smaller one. Reduce the nozzle only one size on a conventional cast-iron head burner. Do not reduce it below the minimum firing rate given on the manufacturer's rating plate.
Flame retention head burners do a much better job of mixing the air and fuel than old cast-iron head burners. They are now almost standard on new units and can also be added to most older ones. A high-static burner will give even better performance. Replacing the burner can increase the seasonal efficiency of an old oil-fired furnace by about 15%. The nozzle must be reduced at least one size and can be reduced even further while maintaining good efficiency. In any case, the flue temperature should not get lower than 400°F for an outside chimney. In the combustion chamber, a ceramic fiber lining can be installed over the present liner.
Always have an experienced contractor check the system's chimney or flue whenever a change is made.